PLC Analog Input Impedance Mismatch Can Cause Abnormal 4–20mA Signals

Direct Answer

PLC analog input impedance mismatch usually means the 4–20mA current loop load is not suitable. If the PLC input resistance is too high, or if display meters, isolators, external resistors or long cables are added in series, the pressure transmitter may not have enough voltage to drive the loop current up to 20mA. The result can be low readings, unstable values, full-scale failure or no signal.

A 4–20mA current loop includes a power supply, transmitter, receiver/controller and wiring. The loop power supply must provide enough voltage to drive all loop loads. Fluke explains that 4–20mA loops are commonly powered by 24VDC and use current variation to represent variables such as pressure, temperature and flow.

PLC Analog Input Impedance Mismatch Can Cause Abnormal 4–20mA Signals
PLC Analog Input Impedance Mismatch Can Cause Abnormal 4–20mA Signals

What Is PLC Analog Input Impedance?

In a 4–20mA input channel, PLC input impedance is the load resistance seen by the current loop. Many analog input modules use an internal resistor to convert current into voltage for A/D conversion.

For example:

Input ResistanceVoltage at 4mAVoltage at 20mA
125Ω0.5V2.5V
250Ω1V5V
500Ω2V10V

AutomationDirect documentation shows some current input modules with 125Ω per channel and others with 250Ω per channel. Rockwell Automation’s Allen-Bradley Micro800 2080-IF4 analog input module also lists 250Ω input impedance in current mode.


Common Problems

ProblemLikely Cause
Signal cannot reach 20mALoop load too high or supply voltage too low
PLC reading is lower than actual pressureInput impedance, scaling or loop voltage issue
Reading jumpsGrounding, interference or wrong input mode
Signal becomes abnormal after adding display/isolatorAdded load causes voltage drop
Transmitter works alone but fails with PLCPLC input configuration or load mismatch
PLC and VFD readings differDifferent scaling, input mode or load path

Fluke notes that newly added loop loads or weak power supplies can prevent the loop from maintaining full current at 20mA, causing the output to level off below 20mA.


How to Diagnose

  1. Check the PLC module manual
    Confirm whether the channel is current input or voltage input, and check the input impedance.
  2. Check whether an external resistor is needed
    If the PLC module is voltage input only, a 250Ω resistor may be used to convert 4–20mA to 1–5V. If the PLC already has current input, adding another resistor may overload the loop.
  3. Calculate loop load
    Include PLC input resistance, cable resistance, isolator load, display load and any added resistor.
  4. Check supply voltage margin
    The power supply must cover the transmitter operating voltage plus the voltage drop across all loop loads at 20mA.
  5. Measure loop current
    Use a loop calibrator, process clamp meter or multimeter to confirm whether the current changes from 4mA to 20mA. Fluke describes using a process clamp meter to verify mA loop current without breaking the loop.
  6. Isolate transmitter and PLC input
    AutomationDirect recommends isolating the transmitter from the PLC input to confirm whether the transmitter is sending the correct signal before blaming the PLC input.

NOIKE-AH Application Solution

NOIKE-AH pressure transmitters can provide continuous pressure feedback to PLC, VFD and control panel systems. NOIKE-AH’s product range includes Pressure Series products such as pressure gauges, pressure switches, pressure sensors and pressure transmitters. (Noike-AH)

Recommended configuration:

  • use a pressure transmitter for continuous pressure feedback;
  • confirm PLC current input mode and input impedance;
  • use a signal splitter or isolator when PLC and VFD both need the same signal;
  • use an intelligent pressure switch for independent alarm and protection;
  • use a digital pressure gauge for local pressure verification.

Conclusion

PLC analog input impedance mismatch can cause low 4–20mA signal, unstable readings, full-scale failure or no signal. The correct troubleshooting process is to check the PLC input type, input impedance, external resistor, transmitter load capability, 24VDC power margin, loop load, grounding and scaling.

NOIKE-AH recommends using pressure transmitters for continuous feedback, intelligent pressure switches for protection and digital pressure gauges for field verification. In pump control panels and constant pressure systems, checking input impedance and loop load before commissioning helps reduce signal problems and after-sales misjudgment.

Table of Contents