How to Set the Start and Stop Pressure of a Pressure Switch

Direct Answer

The start and stop pressure of a pressure switch are called cut-in pressure and cut-out pressure.

Cut-in pressure: the pressure at which the pump starts when system pressure drops.
Cut-out pressure: the pressure at which the pump stops when system pressure rises.

Boshart defines cut-in as the falling-pressure point and cut-out as the rising-pressure point. The difference between them is called the differential.


Why These Settings Matter

If the cut-in pressure is too high, the pump may start too frequently.

If the cut-in pressure is too low, the end user may experience low water pressure.

If the cut-out pressure is too high, the pump may run too long or operate close to its maximum pressure.

If the cut-out pressure is too low, the pressure tank may not store enough water and the pump may cycle more often.

A pressure switch starts or stops the pump at preset system pressures; it stops the pump at cut-out pressure and starts the pump again at cut-in pressure.

Split type digital anti-corrosion pressure switch sensor NT65E series pressure Ports
Split type digital anti-corrosion pressure switch sensor NT65E series

Basic Setting Rules

ParameterRecommendation
Cut-in pressureHigh enough to maintain usable pressure
Cut-out pressureBelow pump and piping safety limits
DifferentialLarge enough to prevent short cycling
Tank prechargeUsually below cut-in pressure
Delay timeHelps avoid false switching from pressure spikes

Pentair notes that many systems keep about a 20 PSI differential between cut-on and cut-off. It also states that cut-off should be at least 5 PSI below the pump dead-head pressure, while cut-on is typically 20 PSI below cut-off.


Step 1: Set the Cut-out Pressure

Cut-out pressure is the upper pressure limit where the pump stops.

Check:

  • maximum pump pressure;
  • pressure rating of pipes, valves, tank and instruments;
  • required system pressure;
  • safety valve setting;
  • whether the pump can reach the target pressure safely.

The cut-out pressure should be high enough for normal use, but lower than the safe limit of the pump and system.


Step 2: Set the Cut-in Pressure

Cut-in pressure is the lower pressure point where the pump starts.

Check:

  • minimum pressure required by the user;
  • pressure loss in long pipelines;
  • pressure tank size;
  • pump start frequency;
  • whether constant pressure is required.

The cut-in pressure should maintain usable water pressure and avoid frequent pump starts.


Step 3: Set the Differential

The differential is the gap between cut-in and cut-out pressure.

Examples:

Cut-inCut-outDifferential
30 PSI50 PSI20 PSI
40 PSI60 PSI20 PSI
2.0 bar3.5 bar1.5 bar
3.0 bar5.0 bar2.0 bar

If the differential is too small, the pump may short cycle. If it is too large, system pressure will fluctuate more.


Step 4: Check Tank Precharge

For systems with a pressure tank, the tank precharge must match the cut-in pressure.

When manufacturer instructions are not available, Boshart recommends setting bladder tank air pressure 2 PSI below the cut-in pressure.

Examples:

Cut-in PressureTank Precharge
30 PSI28 PSI
40 PSI38 PSI
2.0 barabout 1.85 bar
3.0 barabout 2.85 bar

Mechanical Pressure Switch Adjustment

A mechanical pressure switch usually has two adjustment nuts:

AdjustmentFunction
Range nutRaises or lowers both cut-in and cut-out
Differential nutChanges cut-out and differential

Adjusting the range nut changes both cut-in and cut-out while maintaining the same differential; adjusting the differential nut changes the cut-out point while the cut-in point remains the same.

Always disconnect power before adjustment and follow the manufacturer’s instructions.


Smart Pressure Switch Setting

A smart pressure switch is more suitable for pump control panels and automation systems because start pressure, stop pressure, delay and output logic can be set more clearly.

Recommended setting process:

  1. Confirm normal operating pressure.
  2. Set the stop pressure.
  3. Set the start pressure.
  4. Set hysteresis or differential.
  5. Add delay to avoid false switching.
  6. Confirm output signal compatibility.
  7. Test pump start and stop operation.

NOIKE-AH recommends NT30B Intelligent Pressure Switch for pump start/stop control, high/low pressure alarm and pump protection. For continuous pressure feedback, use NT30D Pressure Transmitter. For local pressure reading, add NT53D Digital Pressure Gauge.


Product Combination

ApplicationRecommended ProductFunction
Basic pump controlNT30B Intelligent Pressure SwitchStart/stop pressure setting
Control panel integrationNT30B + NT30DSwitch control + 4–20mA signal
Local pressure checkNT53D Digital Pressure GaugeActual pressure reading
High-reliability pump setNT30B + NT30D + NT53DControl, feedback and display

Conclusion

To set pressure switch start and stop pressure correctly:

  1. Set the cut-out pressure first within pump and system limits.
  2. Set the cut-in pressure based on minimum usable pressure.
  3. Keep a suitable differential to avoid frequent cycling.
  4. Check pressure tank precharge if a tank is used.
  5. Test the control panel logic after adjustment.